New Inventory Daily | Same Day Free Shipping

13k+ reviews

Carlo GavazziSingle-Phase DIN-Rail Energy Meter, 230 V L-N, 5(100) A Direct Connection, M-Bus Port, MID Class B

Condition: Used

Availability:

3 in stock

Single-phase DIN-rail kWh meter for 230 V line-to-neutral circuits, measuring current directly up to 100 A with no external CT. M-Bus port for remote meter reading, dual-tariff digital input, and MID certification for billing. Two DIN modules wide. Sold as 1 piece.

Same day shipment

List Price

$76.46

3 in stock

Prefer eBay? Buy this item on our store (opens in a new tab)

Small green outline icon of a shipping box with a clock, indicating delivery time
Availability

3 in stock

On the Shelf & Ready to Ship

Green shield badge reading "Same-Day Shipping" with box and delivery truck icons
Free Shipping

On all orders

Green shield icon with box and arrow graphic labeled "Free Returns"
Free Returns

No Risk, No Hassle

Specifications

Key Specifications

MFR / BrandCarlo Gavazzi
ModelEM112 DIN AV0 1 X M1 PF A

Technical Specifications

Base NumberEM112-DIN
Industry Termsenergy analyzer; energy analyser; kWh meter; energy meter; sub-meter; DIN rail power meter; MID meter
Common MisspellingsCarlo Gavazi; Carlogavazzi; Carlo-Gavazi; EM112 DIN AVO
Application TypesSub-metering; cost allocation; dual-tariff billing; M-Bus building automation networks; panel energy monitoring
Output Amperage5(100) A measuring range, direct connection
Mpn VariantsEM112DINAV01XM1PFA; EM112-DIN AV0 1 X M1 PF A; EM112DIN.AV0.1.X.M1.PF.A; EM112-DIN.AV0.1.X.M1.PFA
Nominal Rated Input Voltage230 V AC L-N
Part NumberEM112-DIN.AV0.1.X.M1.PF.A
Mounting TypeDIN rail
Communication StandardM-Bus (EN13757-3), 0.3 / 2.4 / 9.6 kbaud
Seller Part Number: AD3B3#LK773D

Product Description

What this part is

A Carlo Gavazzi EM112 single-phase energy analyser in a 2-module DIN-rail housing. It meters active and reactive energy on a 230 V line-to-neutral circuit with the load current passing directly through the meter — no current transformer is needed up to 100 A. The backlit LCD carries three rows of eight digits with an integrated touch keypad, and this version reports over M-Bus.

Decoding the order code

EM112-DIN — single-phase analyser, DIN-rail housing, 2 modules.

AV0 — 230 V L-N AC, 5(100) A direct connection. AV1 is the 120 V variant.

1 — 1-phase, 2-wire system.

X — self powered from the measured voltage, no auxiliary supply.

M1 — M-Bus communication port. S1 is RS485 Modbus, O1 a pulse output.

PF — certified to the MID Directive, Modules B and D, usable for fiscal metrology.

A — power is always integrated in both directions and the total energy register is the MID-certified one.

What these specs mean in practice

The AV0 range code makes this a 230 V meter, self powered from the same 230 V measuring input, with no separate supply terminal. Direct 100 A connection means the busbar or cable runs through the meter, with 25 mm² conductors at the measuring terminals. The A measurement option totalises energy regardless of current direction; the .PF.B variant certifies only the positive register.

Published specifications

System: 1-phase, 2-wire. Nominal Voltage: 230 V L-N AC, −30% +20%. Current: Ib 5 A, Imax 100 A, Imin 0.25 A, direct connection. Start-up Current: 40 mA; start-up voltage 161 V L-N. Active Energy: Class 1 per EN62053-21, Class B per EN50470-3. Reactive Energy: Class 2 per EN62053-23. Current/Voltage Accuracy: ±0.5% of reading. Registers: kWh and kvarh imported/exported, kWh+ on two tariffs. Instantaneous Values: kW, kvar, V, A, PF, Hz, kW demand and demand peak.

Communication: M-Bus per EN13757-3, 0.3 / 2.4 / 9.6 kbaud, up to 250 meters on the network. M-Bus Primary Address: 1 to 250. M-Bus Baud Rate Default: 2.4 kbaud. Secondary M-Bus Address: fixed at production in the 7000 0000 to 7999 9999 range. Demand Integration Time: 1 to 30 minutes, default 1 minute. Digital Input: 1, volt-free contact, for tariff switching. Front LED: 1000 imp/kWh. Sampling: 4096 samples/s.

Insulation: 4000 V AC RMS for 1 minute; overvoltage category III. Operating Temperature: −25 to +55 °C (PF option). Protection: IP51 front, IP20 terminals. Housing: 35 x 63 x 90 mm (W x H x D), 2 DIN modules, self-extinguishing UL 94 V-0. Power Consumption: ≤1 W, ≤8 VA. Weight: approx. 160 g.

Quantity and configuration

Sold as 1 piece.

Interchange guidance

The EM112 family differs in the order-code suffixes. EM112-DIN.AV0.1.X.S1.PF.A is the same meter with RS485 Modbus instead of M-Bus; the .PF.B variants certify only the positive register; AV1 is the 120 V variant. The 1-DIN EM111 is the 45 A version and the 3-DIN EM340 is the three-phase version, related models.

You May Also Like

SINUMERIK 800 Servo Interface / Measuring Circuit Board — Actual-Value Input and Setpoint Output, 20 mm Module Width, Board Only
6FX1121-4BA01

$137.67

4 in stock

Add to cart
Simodrive 610 Power Supply / Infeed Module, 3-Phase 380-480 V AC In, 600 V DC Link, Regenerative
6SC6100-0GE01

$1,288.65

5 in stock

Add to cart
Series One 24 VDC 2 A Output Module — 4 Isolated Fused Sink/Source Circuits, Per-Circuit LEDs, 8 References Consumed

$76.11

7 in stock

Add to cart

Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Assortment of MRO parts including motor, bearing, gears, cylinder and valve

News

Selling an MRO Storeroom in One Lot

Most plants clear a storeroom one part number at a

Selling Surplus Fanuc Boards and Servo Amplifiers

When a CNC machine or a robot leaves the plant,

Additional Resources

Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Get In Touch
Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Get In Touch

Sort

Brand

Price

MPN

Categories

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.