50,000+ Parts In Stock | Ships Today | Free Shipping & Returns

13k+ reviews 99.9% positive eBay feedback · 2,336 ratings in the last 12 months

Pepperl+FuchsHiD20302-Channel Intrinsic-Safety Isolated Barrier / SMART Transmitter Power Supply, 4-20 mA or 1-5 V, HART, Ex ia, SIL 2

Condition: Used

Availability:

1 in stock

Pepperl+Fuchs HiD2030 two-channel intrinsically safe SMART transmitter power supply, 4-20 mA or 1-5 V output, HART on channel 1, SIL 2, Ex ia.

List Price

$160.99

1 in stock

Prefer eBay? Buy this item on our store (opens in a new tab)

Small green outline icon of a shipping box with a clock, indicating delivery time
Availability

1 in stock

On the Shelf & Ready to Ship

Green shield badge reading "Same-Day Shipping" with box and delivery truck icons
Free US Shipping

Ships same day by 6pm ET

Green shield icon with box and arrow graphic labeled "Free Returns"
Free Returns

No Risk, No Hassle

Specifications

Key Specifications

MFR / BrandPepperl+Fuchs
MPNHiD2030
ModelHID2030

Technical Specifications

Base NumberHiD2030
Industry Termsisolated barrier; intrinsic safety barrier; transmitter power supply; SMART transmitter power supply; HART interface device; analog input repeater; galvanic isolator; IS barrier
Common MisspellingsPepperl Fuchs; Pepperl+Fuch; Pepperel Fuchs; Peppert Fuchs; HID 2030; HiD2O30
Application TypesIntrinsically safe 4-20 mA transmitter loops; Zone 0/1/2 and Division 1/2 field devices; HART instrument networks; SIL 2 safety loops; signal splitting to two outputs; process control systems
Output Amperage4 to 20 mA (or 1 to 5 V), load 0 to 650 ohms
Mpn VariantsHiD2030; HID2030; HiD 2030; HiD-2030; 121495
Nominal Rated Input Voltage20.4 to 30 V DC, bus powered via Termination Board
Number Of Rows2 channels
Part NumberHiD2030
Mounting TypeTermination board
Communication StandardHART, BRAIN, Bailey STT02, Foxboro; bidirectional pass-through on channel 1
Seller Part Number: AG1B2#XG3AYV

Product Description

What this part is:

Pepperl+Fuchs HiD2030 (order number 121495) is a two-channel SMART Transmitter Power Supply, an intrinsically safe isolated barrier of the HiD system. It provides a fully floating supply to 2-wire SMART transmitters in a hazardous area and repeats their 4 to 20 mA current into a safe-area load. It also works with 2-wire current sources and can be wired as a signal splitter with one input and two outputs. Unit Quantity: 1 Pc.

Decoding the designation:

HiD — Pepperl+Fuchs HiD system, termination-board mounted modules for large process installations.

2030 — two-channel SMART transmitter power supply with line fault detection.

121495 — Pepperl+Fuchs order number for the HiD2030. HiD2030SK (121500) is the related variant.

Specifications:

Channels: 2, analog input. Functional Safety: SIL 2 per IEC/EN 61508. Supply: 20.4 to 30 V DC, bus powered via Termination Board; 60 mA at 24 V per channel at 20 mA output; 1.05 W dissipation per channel. Input: 4 to 20 mA, current limit typ. 26 mA, input resistance 40 Ω for a current source, min. 15.5 V at 20 mA. Output: 4 to 20 mA or 1 to 5 V (across a 250 Ω 0.1% internal shunt), DIP selectable; load 0 to 650 Ω. Response Time: 70 ms for a 10 to 90% step.

Line Fault Detection: no fault 1 to 23.5 mA; fault below 0.2 mA or above 24 mA. Fault Output: open-collector transistor, common to both channels. Calibrated Accuracy: better than ±0.1% of full scale (current output); linearity ±0.05%; load influence ±0.1% over 0 to 650 Ω; temperature influence ±0.01%/K. Communication: HART, BRAIN, Bailey STT02 and Foxboro protocols; bidirectional digital signals superimposed on the analog value; 0.5 to 40 kHz within 3 dB.

Hazardous Area: II (1)G [Ex ia Ga] IIC and II (1)D [Ex ia Da] IIIC; Uo 26 V, Io 93 mA, Po 605 mW (27.2 V / 93 mA / 633 mW in the splitter configuration); Um 250 V AC. Device-in-zone-2 Marking: II 3G Ex nA IIC T4 Gc, certificate PF 11 CERT 2109 X. Certificates: EU-type examination CESI 02 ATEX 086; IECEx TUN 04.0012; CSA control drawing 366-005CS-12B (cCSAus). Isolation: input/input 60 V peak; input/output and input/supply 375 V peak per IEC 60079-11.

Dimensions and mounting:

Mounting: HiD Termination Board, bus powered. Dimensions: 18 x 114 x 130 mm (W x H x D). Item Weight: approx. 140 g. Degree Of Protection: IP20. Ambient Temperature: −20 to +60 °C; humidity 5 to 90% non-condensing to 35 °C. Indicators: green power LED, red fault LED per channel; 4-position DIP switch; front labelling area. Coding pins 1 and 3 trimmed.

Compatibility and replacement:

Related variant: HiD2030SK (121500), with its own part number and coding. Related HiD modules: HiD2029 and HiD2032.

Frequently asked questions:

Which channel passes HART?

HART passes through on channel 1. Channel 2 carries the analog value without the digital signal.

What output does the HiD2030 provide?

4 to 20 mA or 1 to 5 V, DIP selectable, into a load of 0 to 650 Ω.

What is the hazardous-area rating?

II (1)G [Ex ia Ga] IIC and II (1)D [Ex ia Da] IIIC, SIL 2 per IEC/EN 61508.

You May Also Like

Pepperl+Fuchs HiD2030 transmitter power supply – image 1
HiD2030

$113.99

1 in stock

Add to cart

Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Assortment of MRO parts including motor, bearing, gears, cylinder and valve

News

Servo Amplifier Faulted? Replace, Repair or Rule It Out

Servo amplifier replacement or repair? Rule out the motor, cables

Power Plant Retiring? Sell the Spare Parts First

What happens to power plant spare parts when coal and

Additional Resources

Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Get In Touch
Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Get In Touch

Sort

Brand

Price

MPN

Categories

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.