Two-channel intrinsically safe isolated barrier and SMART transmitter power supply, 4-20 mA or 1-5 V output, HART on channel 1, SIL 2. HiD board mount.
List Price
$113.99

1 in stock
On the Shelf & Ready to Ship
Ships same day by 6pm ET

No Risk, No Hassle
| MFR / Brand | Pepperl+Fuchs |
|---|---|
| MPN | HiD2030 |
| Model | HID2030 |
| Type | Analog Input Repeater |
|---|---|
| Base Number | HiD2030 |
| Industry Terms | isolated barrier; intrinsic safety barrier; transmitter power supply; SMART transmitter power supply; HART interface device; analog input repeater; galvanic isolator; IS barrier |
| Common Misspellings | Pepperl Fuchs; Pepperl+Fuch; Pepperel Fuchs; Peppert Fuchs; HID 2030; HiD2O30 |
| Application Types | Intrinsically safe 4-20 mA transmitter loops; Zone 0/1/2 and Division 1/2 field devices; HART instrument networks; SIL 2 safety loops; signal splitting to two outputs; process control systems |
| Output Amperage | 4 to 20 mA (or 1 to 5 V), load 0 to 650 ohms |
| Mpn Variants | HiD2030; HID2030; HiD 2030; HiD-2030; 121495 |
| Nominal Rated Input Voltage | 20.4 to 30 V DC, bus powered via Termination Board |
| Number Of Rows | 2 channels |
| Part Number | HiD2030 |
| Mounting Type | Termination board |
| Communication Standard | HART, BRAIN, Bailey STT02, Foxboro; bidirectional pass-through on channel 1 |
A Pepperl+Fuchs HiD2030 SMART Transmitter Power Supply, a two-channel intrinsically safe isolated barrier from the HiD system. It provides a fully floating supply to 2-wire SMART transmitters located in a hazardous area and repeats their 4 to 20 mA current into a safe-area load. It also works with 2-wire current sources, and can be wired as a signal splitter taking one input and driving two outputs. Channels: 2. Functional Safety: SIL 2 per IEC/EN 61508. Unit Quantity: 1 Pc, module only.
HiD — Pepperl+Fuchs HiD system, termination-board mounted modules for large process installations.
2030 — two-channel SMART transmitter power supply with line fault detection.
121495 — Pepperl+Fuchs order/part number for the HiD2030.
Supply: 20.4 to 30 V DC, bus powered via Termination Board; 60 mA at 24 V per channel at 20 mA output; 1.05 W dissipation per channel. Input: 4 to 20 mA, current limit typ. 26 mA, input resistance 40 Ω for a current source, min. 15.5 V at 20 mA. Output: 4 to 20 mA or 1 to 5 V (across a 250 Ω 0.1% internal shunt), DIP selectable; load 0 to 650 Ω. Response Time: 70 ms for a 10 to 90% step. Field Transmitter Supply: minimum 14.7 V available at 20 mA. Calibrated Accuracy: better than ±0.1% of full scale (current output); linearity ±0.05%; load influence ±0.1% over 0 to 650 Ω; temperature influence ±0.01%/K.
HART: passes on channel 1; channel 2 carries the analog value; the current-sink terminals 4/7 and 5/6 do not pass HART to the safe area. Communication: bidirectional digital signals superimposed on the analog value; 0.5 to 40 kHz within 3 dB (−6 dB at 100 kHz); supports HART, BRAIN, Bailey STT02 and Foxboro protocols. Line Fault Detection: no fault 1 to 23.5 mA; fault below 0.2 mA or above 24 mA, flagged on a shared open-collector fault bus common to both channels.
Hazardous Area: II (1)G [Ex ia Ga] IIC and II (1)D [Ex ia Da] IIIC; Uo 26 V, Io 93 mA, Po 605 mW (27.2 V / 93 mA / 633 mW in the splitter configuration); Um 250 V AC. Device-in-zone-2 marking: II 3G Ex nA IIC T4 Gc, certificate PF 11 CERT 2109 X. Certificates: EU-type examination CESI 02 ATEX 086; IECEx TUN 04.0012; CSA control drawing 366-005CS-12B (cCSAus). Isolation: input/input 60 V peak; input/output and input/supply 375 V peak per IEC 60079-11.
Indicators: green power LED, red fault LED per channel; 4-position DIP switch; front labelling area. Ambient Temperature: −20 to +60 °C; humidity 5 to 90% non-condensing to 35 °C. Degree of Protection: IP20.
Dimensions: 18 x 114 x 130 mm (W x H x D); mass approx. 140 g. Mounting: bus powered through a HiD Termination Board, a separate item; the module has no DIN rail option and no direct 24 V connection. A HiD Fault Indication Board is a separate item for monitoring the fault bus. Output Selection: all four DIP switches OFF for 4 to 20 mA output, all ON for 1 to 5 V output. Coding pins 1 and 3 trimmed to the safety parameters of this module.
HiD2030SK (121500) is the related variant with its own part number and coding. MPN variants: HiD2030, HID2030, HiD 2030, HiD-2030, 121495.
It powers 2-wire SMART transmitters in a hazardous area and repeats their 4 to 20 mA signal to a safe-area load, with intrinsic-safety isolation.
4 to 20 mA or 1 to 5 V, DIP selectable, load 0 to 650 Ω.
Yes, on channel 1.
Download the Central Surplus seller brochure: what we buy, how it works, how lots are priced, and how sellers get paid within one week.
A dental handpiece spins its bur at roughly 200,000 to 400,000 rpm on ball bearings,
Many industrial loads need torque an electric motor can’t deliver on its own, at a
Our team can locate, cross-reference, and source all parts.
Our team can locate, cross-reference, and source all parts.
Sort
Brand
Price
MPN
Categories