Carlo GavazziEM330-DIN.AV5.3.H.M1.PF.AThree-Phase DIN-Rail Energy Meter, 400-480 V L-L, 5(6) A CT Input, 100-240 V AC/DC Aux Supply, M-Bus, MID Class B

Condition: Used

Availability:

1 in stock

Three-phase DIN-rail energy meter for 400 to 480 V line-to-line systems, metering through external 5 A current transformers rather than direct connection. Runs on a separate 100 to 240 V AC/DC auxiliary supply, reports over M-Bus, and adds a run-hour meter and neutral-current calculation. Three DIN modules wide, current transformers not included. Sold as 1 piece.

Same day shipment

List Price

$103.24

1 in stock

Prefer eBay? Buy this item on our store (opens in a new tab)

Small green outline icon of a shipping box with a clock, indicating delivery time
Availability

1 in stock

On the Shelf & Ready to Ship

Green shield badge reading "Same-Day Shipping" with box and delivery truck icons
Free Shipping

On all orders

Green shield icon with box and arrow graphic labeled "Free Returns"
Free Returns

No Risk, No Hassle

Specifications

Key Specifications

MFR / BrandCarlo Gavazzi
MPNEM330-DIN.AV5.3.H.M1.PF.A
ModelEM330 DIN AV5 3 H M1 PF A

Technical Specifications

Base NumberEM330-DIN
Industry Termsenergy analyzer; energy analyser; three phase kWh meter; CT energy meter; DIN rail power meter; MID meter; sub-meter
Common MisspellingsCarlo Gavazi; Carlogavazzi; Carlo-Gavazi; EM330 DIN AV53
Application TypesThree-phase sub-metering; cost allocation; 480 V switchgear metering; CT-connected feeder monitoring; M-Bus building automation networks
Output Amperage5(6) A CT secondary input, max CT x VT 1000
Mpn VariantsEM330-DINAV53HM1PFA; EM330 DIN AV5 3 H M1 PF A; EM330DIN.AV5.3.H.M1.PF.A; EM330-DIN.AV5.3.H.M1.PFA
Nominal Rated Input Voltage400 to 480 V AC L-L measuring input; 100 to 240 V AC/DC auxiliary supply
Part NumberEM330-DIN.AV5.3.H.M1.PF.A
Mounting TypeDIN rail
Communication StandardM-Bus (EN13757-1), 0.3 / 2.4 / 9.6 kbaud
Seller Part Number: AD2B1#TM4FHI

Product Description

What this part is

A Carlo Gavazzi EM330 three-phase energy meter in a 3-module DIN-rail housing. Unlike the direct-connect EM340, this one measures current through external 5 A current transformers, so it sizes to whatever the CT ratio is rather than to a 65 A limit. Backlit LCD with three rows of eight digits, three touch keys, per-phase as well as system readings, and an M-Bus port for remote reading.

Decoding the order code

Read EM330-DIN.AV5.3.H.M1.PF.A left to right as model, range, system, power supply, output, option, measurement.

EM330-DIN – three-phase meter, DIN-rail housing, 3 modules, CT inputAV5 – 400 to 480 V L-L AC (230 to 277 V L-N), 5(6) A via CT3 – 3-phase, 3- or 4-wire (the non-certified X version also does 2-phase 3-wire and 1-phase 2-wire)H – auxiliary power supply, 100 to 240 V AC/DC ±10%M1 – M-Bus communication port (S1 would be RS485 Modbus, O1 a pulse output)PF – certified to the MID Directive, Modules B and D, usable for fiscal metrologyA – power is always integrated in both directions and that total register is the MID-certified one

What these specs mean in practice

Two things separate this from the more common EM340. First, it is CT-connected: the 5(6) A rating is the secondary current, not the load, and you must supply three 5 A-secondary current transformers and program the CT ratio into the meter. Nothing is metered until that ratio is set. Second, the H suffix means it is not self powered — a 100 to 240 V AC/DC auxiliary supply has to be wired to its own terminals, which is an advantage on a 480 V system where you would not want the meter to draw from the measured phases. Maximum CT x VT product is 1000. The A measurement option totalises regardless of current direction, so it will not separate import from export.

Published specifications

System: 3-phase, 3- or 4-wire, CT connectionNominal voltage: 400 to 480 V L-L AC (230 to 277 V L-N)Current: In 5 A, Imax 6 A, Imin 0.25 A via CT; max CT x VT = 1000Auxiliary supply: 100 to 240 V AC/DC ±10%, ≤1 W / ≤8 VAStart-up current: 10 mA; start-up voltage 90 V L-NActive energy: Class 1 per EN62053-21, Class B per EN50470-3Reactive energy: Class 2 per EN62053-23Current/voltage accuracy: ±0.5% of reading (L-L voltage ±1%); frequency ±0.2%Active power accuracy: ±1% of reading; reactive power ±2%System values: kW, kvar, kVA, V L-L, V L-N, PF, Hz, kW demand and demand peakPhase values: kW, kvar, kVA, V L-L, V L-N, A, PF, plus kWh per phaseExtras: run-hour meter, calculated neutral current, phase-sequence and wrong-connection detectionCommunication: M-Bus per EN13757-1, 0.3 / 2.4 / 9.6 kbaud, up to 250 meters, ID range 9000 0000 to 9999 9999Digital input: 1, volt-free contact, for tariff switchingSampling: 4096 samples/sInsulation: 4000 V AC RMS for 1 minute; overvoltage category IIIOperating temperature: −25 to +55 °C (PF option)Protection: IP51 front, IP20 terminals; tamper-proof sealing covers included, two seal pointsHousing: 54 x 90 x 63 mm (W x H x D), 3 DIN modules, self-extinguishing polycarbonateVoltage input terminals: 1 to 4 mm², 0.6 Nm; other terminals 1.5 mm², 0.4 NmApprovals: CE, MID (PF only), cULus to UL61010-1Weight: approx. 240 g

Quantity and configuration

Sold as 1 piece — the meter only. Current transformers are not included and are required; so is the auxiliary supply wiring. Sealing covers are part of the standard product; confirm what is present before relying on them for a revenue installation.

Installation and setup notes

Set the CT ratio (page P4) and, if voltage transformers are used, the VT ratio (P5) before commissioning — readings scale off those two numbers and the front LED pulse weight is derived from their product. On M1 units also set the M-Bus primary address (P13, 1 to 250) and baud rate (P15, default 2.4 kbaud). The built-in wrong-connection check flags reversed CTs and out-of-order phases, but it only works on loads with PF above 0.766 inductive or 0.996 capacitive and at least 10% of rated primary current. Menus are password protected, default 0000; Measurement and Home-page menus are locked on PF units.

Interchange guidance

The EM330 and EM340 look alike and are not interchangeable: the EM340 is direct-connect 5(65) A at 208 to 400 V L-L and self powered, while this EM330 needs CTs and a separate auxiliary supply. Within the EM330 range, S1 and O1 replace the M-Bus port with RS485 Modbus or a pulse output, and the .PF.B version separates imported from exported energy. The ET330 is the transducer version with no display. Treat all of those as related models rather than equivalents.

You May Also Like

Series One 4-Circuit DC Output Module, 5–24 VDC 2 A per Point, Individually Isolated and Individually Fused, Sink or Source

$52.54

4 in stock

Add to cart
M18 x 1 Inductive Proximity Sensor, Flush Mount, 7 mm Range, PNP NO, 10-36 V DC, IP67, 5 m PUR Cable

$41.61

5 in stock

Add to cart

Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Assortment of MRO parts including motor, bearing, gears, cylinder and valve

News

Selling an MRO Storeroom in One Lot

Most plants clear a storeroom one part number at a

Selling Surplus Fanuc Boards and Servo Amplifiers

When a CNC machine or a robot leaves the plant,

Additional Resources

Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Get In Touch
Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Get In Touch

Sort

Brand

Price

MPN

Categories

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.