New Inventory Daily | Same Day Free Shipping

12,984 ratings on eBay See our eBay feedback →

Pepperl+Fuchs1214952-Channel Intrinsic-Safety Isolated Barrier / SMART Transmitter Power Supply, 4-20 mA or 1-5 V, HART, Ex ia, SIL 2

Condition: Used
Condition Note: See Pictures

Availability:

1 in stock

Two-channel intrinsic-safety isolated barrier that powers 2-wire 4-20 mA SMART transmitters in Zone 0/1/2 or Division 1/2 and repeats the signal to a safe-area load, passing HART both ways on channel 1. DIP-selectable 4-20 mA or 1-5 V output, line fault detection, SIL 2 capable. Plugs into a HiD Termination Board, which is not included. Sold as 1 piece.

Same day shipment

List Price

$118.96

1 in stock

Availability

1 in stock

On the Shelf & Ready to Ship

Free Shipping

On all orders

Free Returns

No Risk, No Hassle

Also Available From:

Specifications

Key Specifications

MFR / BrandPepperl+Fuchs
MPN121495
ModelHID2030

Technical Specifications

ConditionUsed
TypeAnalog Input Repeater
Base NumberHiD2030
Industry Termsisolated barrier; intrinsic safety barrier; transmitter power supply; SMART transmitter power supply; HART interface device; analog input repeater; galvanic isolator; IS barrier
Common MisspellingsPepperl Fuchs; Pepperl+Fuch; Pepperel Fuchs; Peppert Fuchs; HID 2030; HiD2O30
Application TypesIntrinsically safe 4-20 mA transmitter loops; Zone 0/1/2 and Division 1/2 field devices; HART instrument networks; SIL 2 safety loops; signal splitting to two outputs; process control systems
Condition NoteSee Pictures
Output Amperage4 to 20 mA (or 1 to 5 V), load 0 to 650 ohms
Mpn VariantsHiD2030; HID2030; HiD 2030; HiD-2030; 121495
Additional AttributesSIL 2 per IEC/EN 61508; Uo 26 V, Io 93 mA, Po 605 mW; Um 250 V AC; II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC; device-in-zone-2 II 3G Ex nA IIC T4 Gc; CESI 02 ATEX 086; IECEx TUN 04.0012; cCSAus control drawing 366-005CS-12B; line fault detection 0.2-24 mA window; open-collector collective fault output; accuracy 0.1% FS, linearity 0.05% FS; 70 ms response; 14.7 V min at field transmitter; IP20; 18 x 114 x 130 mm; approx. 140 g; coding pins 1 and 3 trimmed
Min Temp-20 C
Max Temp60 C
Nominal Rated Input Voltage20.4 to 30 V DC, bus powered via Termination Board
Number Of Rows2 channels
Mounting ArrangementHiD Termination Board (not included); not DIN-rail mountable
Design UnitsMetric
Part NumberHiD2030
Mounting TypeTermination board
Communication StandardHART, BRAIN, Bailey STT02, Foxboro; bidirectional pass-through on channel 1

Cross-References

Cross Reference 1Pepperl+Fuchs 121495
Seller Part Number: AE2B5#3F9WET

Product Description

What this part is:
A Pepperl+Fuchs HiD2030 SMART Transmitter Power Supply — a two-channel intrinsically safe isolated barrier from the HiD system. It provides a fully floating supply to 2-wire SMART transmitters located in a hazardous area and repeats their 4 to 20 mA current into a safe-area load, so the control system sees an isolated signal. It also works with 2-wire current sources, and can be wired as a signal splitter taking one input and driving two outputs.

Correcting the source data:
Pepperl+Fuchs classifies this module as a SMART Transmitter Power Supply and 2-channel isolated barrier, not simply an analog input repeater. That distinction matters when you specify it: it supplies the transmitter as well as repeating the signal, and its purpose is intrinsic-safety isolation between a hazardous-area field device and a safe-area input. If what you need is only a signal repeater on a safe-area circuit, this is more device than the job requires — and if what you need is Ex isolation, a plain repeater will not do.

Decoding the designation:
HiD – Pepperl+Fuchs HiD system, termination-board mounted modules for large process installations2030 – two-channel SMART transmitter power supply with line fault detection121495 – Pepperl+Fuchs order/part number for the HiD2030; HiD2030SK (121500) is the related variant

What these specs mean in practice:
Three things decide whether this drops into your system. First, it is bus powered through a HiD Termination Board, not through terminals on the module — there is no DIN rail option and no direct 24 V connection on the module itself. Second, HART pass-through works on channel 1 only; channel 2 carries the analog value but not the digital signal, and the current-sink terminals 4/7 and 5/6 do not pass HART to the safe area at all. Third, the field transmitter sees a minimum of 14.7 V at 20 mA, which is the number to check against your transmitter’s lift-off voltage before committing. Line fault detection flags an input outside 0.2 to 24 mA on a shared open-collector fault bus, so the fault signal is collective across both channels rather than per channel.

Published specifications:
Channels: 2, analog inputFunctional safety: SIL 2 per IEC/EN 61508Supply: 20.4 to 30 V DC, bus powered via Termination Board; 60 mA at 24 V per channel at 20 mA output; 1.05 W dissipation per channelInput: 4 to 20 mA, current limit typ. 26 mA, input resistance 40 Ω for a current source, min. 15.5 V at 20 mAField transmitter supply: minimum 14.7 V available at 20 mAOutput: 4 to 20 mA or 1 to 5 V (across a 250 Ω 0.1% internal shunt), DIP selectable; load 0 to 650 ΩResponse time: 70 ms for a 10 to 90% stepLine fault detection: no fault 1 to 23.5 mA; fault below 0.2 mA or above 24 mAFault output: open-collector transistor, common to both channels, collective error messageCalibrated accuracy: better than ±0.1% of full scale (current output); linearity ±0.05%; load influence ±0.1% over 0 to 650 Ω; temperature influence ±0.01%/KCommunication: bidirectional digital signals superimposed on the analog value; 0.5 to 40 kHz within 3 dB (−6 dB at 100 kHz); supports HART, BRAIN, Bailey STT02 and Foxboro protocolsHazardous area: II (1)G [Ex ia Ga] IIC and II (1)D [Ex ia Da] IIIC; Uo 26 V, Io 93 mA, Po 605 mW (27.2 V / 93 mA / 633 mW in the splitter configuration); Um 250 V ACDevice-in-zone-2 marking: II 3G Ex nA IIC T4 Gc, certificate PF 11 CERT 2109 XCertificates: EU-type examination CESI 02 ATEX 086; IECEx TUN 04.0012; CSA control drawing 366-005CS-12B (cCSAus)Isolation: input/input 60 V peak; input/output and input/supply 375 V peak per IEC 60079-11Indicators: green power LED, red fault LED per channel; 4-position DIP switch; front labelling areaAmbient temperature: −20 to +60 °C; humidity 5 to 90% non-condensing to 35 °CDegree of protection: IP20Dimensions: 18 x 114 x 130 mm (W x H x D); mass approx. 140 gCoding pins 1 and 3 trimmed

Quantity and configuration:
Sold as 1 piece — the module only. The HiD Termination Board is not included and is required: the module has no independent power or field terminals and cannot be mounted on DIN rail. A Fault Indication Board, if you want the fault bus monitored, is also separate.

Installation and setup notes:
To change the output between 4 to 20 mA and 1 to 5 V, push the red Quick Lok bars on each side of the module upward, lift it off the termination board and set all four DIP switches: all OFF for current output, all ON for voltage output. The coding pins are trimmed to match this module’s safety parameters and must not be altered — that is what stops a module with different Ex parameters being plugged into the same slot. Where HART access matters, plan the loop so the smart device sits on channel 1.

Interchange guidance:
HiD and K-System modules are not interchangeable: a KFD2-STC series barrier mounts on 35 mm DIN rail with its own terminals, while the HiD2030 needs a termination board, so the two are different installation systems entirely even where the signal function matches. HiD2030SK is the closely related variant and carries its own part number and coding; check the coding pins and the termination board slot before assuming it fits. HiD2029 and HiD2032 are neighbouring modules in the same family with different channel counts and functions.

You May Also Like

2-Channel Intrinsic-Safety Isolated Barrier / SMART Transmitter Power Supply, 4-20 mA or 1-5 V, HART, Ex ia, SIL 2
121495

$168.78

1 in stock

Add to cart

Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

News

Excess MRO Inventory Depreciating on Your Shelf

The dead stock on your shop floor is not an

MRO Parts Fulfillment. What Fast Really Means

A shipping cutoff banner measures a vendor’s dock. It tells

Additional Resources

Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Get In Touch
Need help finding the right part?

Our team can locate, cross-reference, and source all parts.

Get In Touch

Sort

Brand

Price

MPN

Categories

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.